A company's greatest investment is not the equipment that's behind the panel door; top priority is to offer the ultimate protection for the electricians, engineers and inspectors who risk their lives every day doing their jobs.
The ClirVu® coating - exclusive to Fluke infrared windows - seals the optic prior to assembly to protect against moisture degradation making it perfect for very hot and very cold environments.
Each Fluke infrared window is delivered with an identification plate attached for unique, on-site numbering for rapid location confirmation and faster repairs.
For a security key access option see the CV201 IR Window.
The CV Series of infrared windows are also available in 75 mm (3 in) and 95 mm (4 in) sizes.
Installs and grounds in less than 5 minutes
Save time with quick and easy installation with the CV Series – 5 minutes or less.
Work more efficiently with Fluke ClirVu® CV200 50 mm (2 in) Infrared Windows
Includes:
General Specifications | |
Size | 50 mm (2 in) |
Voltage range | Any |
NEMA environment type | Type 4/12 (indoor/outdoor) |
AutoGround™ | Yes |
ClirVu® optic | Yes |
Operating temperature | -40°C to +232°C (-40° F to +450°F) and +260°C (500°F) intermittent |
Compatible with all Fluke cameras | Yes |
Jam nut locking system | Yes |
Cover and fastener permanently attached | Yes |
Single-hole install | Yes |
Hand turn and security key door latch options | Yes |
Visual inspection and fusion capable | Yes |
Short/Mid/Long-wave IR and UV capable | Yes |
Ratings and Testing | |
Arc-tested (IEEE C37.20.7) | 63 kA for 30 cycles @ 60 Hz at KEMA |
UL 50 V component recognition | Yes |
UL 50 /NEMA environmental rating | NEMA Type 4/12 |
UL1558 | Yes |
CSA C22.2 No. | Yes |
CSA type rating | Type 4 |
IP rating | IP67 at TUV |
Lloyds register | Up to 11 kV marine switchgear, indoor or outdoor (offshore only) |
Vibration rating | IEC60068-2-6 at TUV |
Humidity rating | IEC60068-2-3 at TUV |
Install | |
Actual mounting hole diameter required | 61.37 mm (2.416 in) |
Greenlee® punch kit = punch/die | 76BB = 441AV/442AV |
Recommended max panel thickness | 10 gage |
Overall window height | 112.9 mm (4.45 in) |
Overall window width | 83.0 mm (3.27 in) |
Overall window thickness | 16.2 mm (0.64 in) |
Door latch | Hand Turn |
Optics | |
Optic insert diameter | 50 mm (1.97 in) |
Viewing aperture diameter | 42.93 mm (1.690 in) |
Viewing aperture area | 1445 mm2 (2.24 in2) |
Thickness | 2 mm (0.08 in) |
Other | |
Warranty | Lifetime replacement against manufacturing defects |