Built with the Fluke Connect® mobile app and desktop software compatibility, this logger provides you with the data you need to make critical power quality and energy decisions in actual time. Ideal for conducting energy studies and basic power quality logging, this logger automatically captures and logs over 500 power quality parameters which give you more visibility into the data you need to optimise system reliability and savings.
An optimised user interface, flexible current probes, and an intelligent measurement verification function that allows you to reduce measurement errors by digitally verifying and correcting common connection errors makes setup easier than ever and reduces measurement uncertainty. Access and share data remotely with your team via the Fluke Connect® app so you can maintain safer working distances and make critical decisions in real-time, reducing the need for protective equipment, site visits and check-ins. You can also quickly and easily chart and graph measurements to help identify issues and create detailed reports with the included Fluke Energy Analyse Plus software package.
If you're looking for a power logger with the same great energy study capabilities and more advanced power quality logging capabilities, this energy logger is the ideal choice.
Accuracy | |
Voltage | Range: 1000 V Resolution: 0.1 V Intrinsic Accuracy at Reference Conditions: ±(0.2% + 0.01%) |
i17xx-flex 1500 12" | Range: 150 , 1500 A Resolution: 0.1, 1 A Intrinsic Accuracy at Reference Conditions: ±(1% + 0.02%), ±(1% + 0.02%) |
i17xx-flex 3000 24" | Range: 300 , 3000 A Resolution: 1, 10 A Intrinsic Accuracy at Reference Conditions: ±(1% + 0.03%), ±(1% + 0.03%) |
i17xx-flex 6000 36" | Range: 600 , 6000 A Resolution: 1, 10 A Intrinsic Accuracy at Reference Conditions: ±(1.5% + 0.03%), ±(1.5% + 0.03%) |
i40s-EL Clamp | Range: 4 , 40 A Resolution: 1, 10 mA Intrinsic Accuracy at Reference Conditions: ±(0.7% + 0.02%), ±(0.7% + 0.02%) |
Frequency | Range: 42.5 Hz to 69 Hz Resolution: 0.01 Hz Intrinsic Accuracy at Reference Conditions: ±(0.1%) |
Auxillary Input | Range: ±10 V dc Resolution: 0.1 mV Intrinsic Accuracy at Reference Conditions: ±(0.2% + 0.02%) |
Voltage Min/Max | Range: 1000 V Resolution: 0.1 V Intrinsic Accuracy at Reference Conditions: ±(1% + 0.1%) |
Current Min/Max | Range: Defined by accessory Resolution: Defined by accessory Intrinsic Accuracy at Reference Conditions: ±(5% + 0.2%) |
THD on Voltage | Range: 1000% Resolution: 0.1% Intrinsic Accuracy at Reference Conditions: ±0.5 |
THD on Current | Range: 1000% Resolution: 0.1% Intrinsic Accuracy at Reference Conditions: ±0.5 |
Voltage Harmonics 2nd to 50th | Range: 1000 V Resolution: 0.1 V Intrinsic Accuracy at Reference Conditions: ≤10 V: ±5% of reading, <10 V: ±0.5 V |
Current Harmonics 2nd to 50th | Range: Defined by accessory Resolution: Defined by accessory Intrinsic Accuracy at Reference Conditions: ≤3% of current range: ±5% of reading, <3% of current range: ±0.15% of range |
Unbalance | Range: 100% Resolution: 0.1% Intrinsic Accuracy at Reference Conditions: ±0.2 |